| AARG | RELIABILITY INDICATOR | NOT ESTABLISHED |
| ABHP | OVERALL LENGTH | 8.000 INCHES MAXIMUM |
| ABKQ | CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO LENGTH | 4.120 INCHES NOMINAL SINGLE MOUNTING FACILITY SINGLE CENTER GROUP |
| ABKR | CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO WIDTH | 4.500 INCHES NOMINAL SINGLE MOUNTING FACILITY SINGLE CENTER GROUP |
| ABKW | OVERALL HEIGHT | 5.620 INCHES MAXIMUM |
| ABMK | OVERALL WIDTH | 5.500 INCHES MAXIMUM |
| ABTD | MOUNTING SLOT WIDTH | 0.280 INCHES NOMINAL SINGLE GROUP |
| ACZB | FREQUENCY RATING | 59.0 HERTZ MINIMUM AND 61.0 HERTZ MAXIMUM SINGLE COMPONENT |
| ACZC | INPUT-OUTPUT PHASE RELATIONSHIP | THREE PHASE TO SINGLE PHASE AND THREE PHASE TO THREE PHASE SINGLE COMPONENT |
| ACZD | TRANSFORMER WINDING CONNECTION TYPE | DELTA-DELTA AND DELTA-WYE |
| ACZX | WINDING SHIELDING METHOD | INTERNAL SHIELD GROUNDED TO CORE AND BROUGHT OUT TO TERMINAL SINGLE COMPONENT |
| AEHZ | MAXIMUM OPERATING TEMP | 50.0 CELSIUS |
| AKNA | INCLOSURE TYPE | FULLY INCLOSED |
| AKPV | MOUNTING FACILITY QUANTITY | 4 SINGLE GROUP |
| AXGY | MOUNTING METHOD | FLANGE AND SLOT SINGLE GROUP |
| BPLC | WINDING FUNCTION AND QUANTITY | 1 PRIMARY AND 8 SECONDARY SINGLE COMPONENT |
| CRBZ | WINDING OPERATING CURRENT | 1.0 AMPERES DC MAXIMUM SINGLE COMPONENT THIRD SECONDARY |
| CRBZ | WINDING OPERATING CURRENT | 3.0 AMPERES DC MAXIMUM SINGLE COMPONENT FIRST SECONDARY |
| CRBZ | WINDING OPERATING CURRENT | 5.0 AMPERES DC MAXIMUM SINGLE COMPONENT SECOND SECONDARY |
| CWJS | WINDING OPERATING VOLTAGE | 103.50 AC VOLTS MINIMUM AND 126.50 AC VOLTS MAXIMUM SINGLE COMPONENT SINGLE PRIMARY |
| CWJS | WINDING OPERATING VOLTAGE | 17.10 DC VOLTS MINIMUM AND 18.90 DC VOLTS MAXIMUM SINGLE COMPONENT FIRST SECONDARY |
| CWJS | WINDING OPERATING VOLTAGE | 38.00 DC VOLTS MINIMUM AND 42.00 DC VOLTS MAXIMUM SINGLE COMPONENT THIRD SECONDARY |
| CWJS | WINDING OPERATING VOLTAGE | 80.75 AC VOLTS MINIMUM AND 89.25 AC VOLTS MAXIMUM SINGLE COMPONENT FOURTH SECONDARY |
| CWJS | WINDING OPERATING VOLTAGE | 9.50 DC VOLTS MINIMUM AND 10.50 DC VOLTS MAXIMUM SINGLE COMPONENT SECOND SECONDARY |
| FEAT | SPECIAL FEATURES | 1PRIMARY WINDING; 8SECONDARY WINDINGS; ALL SECONDARY WINDINGS VOLTAGE AND CURRENTS RECTIFIED |
| TTQY | TERMINAL TYPE AND QUANTITY | 30 QUICK DISCONNECT, MALE |