| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 10.120 INCHES NOMINAL |
| ADAT | BODY WIDTH | 8.250 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 4.080 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.120 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.880 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.250 INCHES NOMINAL |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.220 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED STUD(S) |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| CMLP | THREAD QUANTITY PER INCH | 13 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 400.0 AMPERES AC AND 400.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 150000.0 AC AND 220000.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +3000.0 TO 4800.0 AC ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.500 INCHES |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE PROOF AND FUNGUS PROOF |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
| CRTK | SWITCH TERMINAL TYPE | WIRE LEAD |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |