| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 5.120 INCHES MINIMUM AND 5.130 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 2.067 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.545 INCHES MINIMUM AND 2.555 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.021 INCHES MINIMUM AND 1.031 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.745 INCHES MINIMUM AND 2.755 INCHES MAXIMUM |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.021 INCHES MINIMUM AND 1.031 INCHES MAXIMUM |
| AJEC | BOSS HEIGHT | 0.215 INCHES MINIMUM AND 0.225 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.545 INCHES MINIMUM AND 3.555 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 2 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 9.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC AND 480.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT AND 130.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |